[Beowulf] Re: UPS & power supply instability
Many of your questions may have already been answered in earlier discussions or in the FAQ. The search results page will indicate current discussions as well as past list serves, articles, and papers.
David Kewley kewley at gps.caltech.eduThu Sep 29 17:43:38 PDT 2005
- Previous message: [Beowulf] Re: UPS & power supply instability
- Next message: [Beowulf] Re: UPS & power supply instability
- Messages sorted by: [ date ] [ thread ] [ subject ] [ author ]
On Thursday 29 September 2005 15:45, David Mathog wrote: > > > I liked Jim's idea of trying a > > > balanced, large resistive load on the lines. A heater, an > > > electric range. > > > > I want to say (but am not sure at the moment) that the > > instabilities show up > > at around 140kW. I don't have 140kW of resistors available easily, > > let alone a full-power load of 350kW. > > Sure, but if things are really, really, badly screwed up one > might see a largish neutral current, percentage wise, no > matter what size the resistive load. Try three matched > space heaters (one per phase) and see if the neutral current > is zero. If it isn't then you (or your electrician) can > diagnose at least part of this problem without having to plug > in a full load. Now that *is* an interesting idea, and a doable one. I can certainly try that, although I don't know exactly when. ;) > For the experts out there: could a huge iron pipe, or a lot > of iron rebar, produce this much of an inductive load if these were > located just below the floor, say 6 inches from the power > lines running to the racks? The lab in question is on > the bottom floor of the building so there could conceivably > be something like that underneath it. I'm thinking not, but > then I've never worked with the kinds of currents that are present > here. If this magnitude of effect is important, then we probably should also think further about ground currents in the room, which we have measured at various points. We have eliminated the one place where a delta-wye transformer secondary's neutral was tied to ground at two places. Now the PDUs do not indicate any ground current, whereas with the two-tie topology they did. All the rest of the equipment (e.g. HVAC) is 3-phase, so should not be a problem. But as much as 2-3A *is* flowing when we look with clamp-on meters at various ground cables. This ground current is likely related to the fact that there are three ground paths to the room, all referred back to the same earth electrode point. These paths are likely tied together in the room as well as at the remote earth electrode, creating a loop. One ground path travels with the computer power lines. A second is grounding the raised floor metal components. And a third ground travels with the power to the HVAC systems. To complicate that third path, the HVAC ground path splits between the HVAC main breaker box and the HVACs, one path going through a devoted UPS, and one directly connected to the HVACs (the two branches power different subcomponents of the HVAC). Very likely the HVAC and PDU chasses are tied to the floor grid, thereby connecting all 2-3 paths back to the earth electrode. If there's no leakage between neutral and ground anywhere, then the only other mechanism I can think of that would cause these currents is induction. Can induction typically produce currents this large on a ~1000 ft^3 ground loop? Am I missing something? David
- Previous message: [Beowulf] Re: UPS & power supply instability
- Next message: [Beowulf] Re: UPS & power supply instability
- Messages sorted by: [ date ] [ thread ] [ subject ] [ author ]
More information about the Beowulf mailing list